Hardware | Processor Status LEDs (Gateway)
Status LEDs (Fieldbus) | Altera Cyclone V SoC with dual-core ARM Cortex-A9 PWR (power supply), RUN (operation), ERR (error), CFG (configuration and update) SF (system fault), BF (bus fault) |
Interfaces and Connectors | Ethernet
PROFIBUS PA | 2 * IEEE 802.3 100BASE-TX / 10BASE-T, embedded PROFINET switch for daisy chain topology Connectors: RJ45 Protocol: PROFINET RT / IRT, Support of PROFINET redundancy protocols RESTful API interface for device configuration Up to 4 PROFIBUS PA (MBP) segments (refer to the section “Order Numbers”), Bus-powered Medium Attachment Unit (MAU): Fieldbus voltage range: 9 VDC ... 32 VDC, current consumption 10 mA, Connectors: 3-position screw connection, galvanically isolated |
Physical Properties | Dimensions (H x W x D) Weight Power Supply
Operating / Storage Temperature Relative Humidity Cooling Coating Mounting Protection Class | 100 mm x 35 mm x 105 mm About 0.25 kg 18 VDC ... 32 VDC; SELV/PELV power supply mandatory Typical input current: 200 mA, maximum input current: 1 A (allowing for in-rush current at switch-on) No power supply to PROFIBUS PA segments through pnGate PA -40 °C ... +70 °C / -40 °C ... +85 °C (see detailed mounting description in user manual) 10 % ... 95 %, non-condensing Convection, no fan Conformal coating based on ANSI / ISA-S71.04 G3 DIN rail 35 mm IP20 |