Building a safe and secure embedded world

Gateway for OPC UA and MQTT Communication Access to Modbus TCP PLCs

uaGate MB

Access to Data in Modbus PLCs from OPC UA Applications

  • Access to Modbus controllers, e.g. from Schneider Electric, Wago, Beckhoff, Phoenix Contact, etc.
  • Integration of higher-level management systems like ERP, MES or SCADA using integrated OPC UA Server providing open, platform-independent and market-proven communication
  • Easy local and global access to field data and routing through firewalls
  • Especially dedicated to retrofit upgrades, thus protecting former investments
  • No need for software updates, operating system patches and PC updates resulting in years of failure-free operation
  • Minimal PLC programming for register setup required
  • No dedicated PC required

PLC Project Data Available for Further Processing

  • Symbol import from user-edited text file
  • Easy setup of OPC UA Server requiring only a few steps for accessing data in Modbus PLCs
  • Web-based interface for gateway configuration

Industry-proven Security

  • Physically separated interfaces and separate configuration rights for OT and IT networks preventing intrusions
  • Supporting security standards as SSL/TLS and X.509 certificates
  • OPC UA compliant data encryption and user authentification
  • Security supported for MQTT communication with private and public clouds
HardwareProcessorAltera Cyclone V SoC with Dual-core ARM Cortex-A9
 Connectors2 x IEEE 802.3 100BASE-TX/10BASE-T (independent interfaces)
 Status LEDsPWR (power supply), RUN (running), ERR (error), SYS (configuration)
 Dimensions (H x W x D)100 mm x 22.5 mm x 105 mm
 Power Supply18 VDC ... 32 VDC, SELV/PELV supply mandatory Typically 200 mA, maximum 1 A at switch-on
 Operating Temperature, Horizontal DIN Rail Installation-40 °C .. 50 °C (0 mm minimum distance)
-40 °C .. 55 °C (22.5 mm minimum distance)
 Operating Temperature, Vertical DIN Rail Installation-40 °C .. 35 °C (0 mm minimum distance)
-40 °C .. 40 °C (22.5 mm minimum distance)
 Storage Temperature-40 °C .. 85 °C
 Relative Humidity10 % ... 90 %, non-condensing
 WeightAbout 0.2 kg
 MountingDIN Rail (35 mm)
 HousingPhoenix Contact ME MAX
 Protection ClassIP20
SoftwareProtocolsModbus TCP, OPC UA (Server, 20,000 items in total), MQTT (Publisher, up to 1,000 topics)
 Supported ControllersModbus TCP controllers, e.g. from Schneider Electric, Wago, Beckhoff, Phoenix Contact, etc.
ConformityEmissionEC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 55011, Group 1, Class A 
EC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 55022, Class A 
EC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 61000, Part 6-4 
FCC CFR45, Part 15 Section 15.107 and 15.109 (Class A), 
VCCI Class A Information Technology Equipment 2002
 ImmunityEC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 61000, Part 6-2
CertificationsCE, FCC, RoHS
GAA-YE-145133uaGate MB

 

Scope of Delivery

HardwareuaGate MB
SoftwareTool for configuration over integrated web interface
DocumentationQuick Startup Guide (printed documentation)